COMMISSIONING
100 Service Manual Part No.: 4417340 Revision 1
954 SmartServo FlexLine
7.3.6.3.2 Relay Mode
Each individual relay can be set to be energized or de-energized during
operation, by setting the [Relay Mode] entity to <Energized> or <De-
energized> respectively.
If the [Relay Mode] entity is set to <Energized>, the relay coil will be
energized when the relay state is <Deactivated>, and the relay coil will
be de-energized when the relay state is <Activated>.
If the [Relay Mode] entity is set to <De-Energized>, the relay coil will be
de-energized when the relay state is <Deactivated>, and the relay coil
will be energized when the relay state is <Activated>.
The <Energized> option is used for fail-safe operation whereas the <De-
Energized> option is used for non-fail-safe operation.
Set each individual relay to the required configuration, by selecting
the proper entities. See also next overview (fail-safe configuration is
coloured).
Physically
Configured
Relay Mode Relay State
Physical Result
Normally Open
(NO)
De-Energized Activated Closed
Deactivated Open
Energized Activated Open
Deactivated Closed
Normally Closed
(NC)
De-Energized Activated Open
Deactivated Closed
Energized Activated Closed
Deactivated Open

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell FlexLine SmartServo 954 and is the answer not in the manual?

Honeywell FlexLine SmartServo 954 Specifications

General IconGeneral
BrandHoneywell
ModelFlexLine SmartServo 954
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals