COMMISSIONING
154 Service Manual Part No.: 4417340 Revision 1
954 SmartServo FlexLine
7.3.9.5 Board Commissioning
7.3.9.5.1 Basic Configurable Entities Overview
Basic configuration entities of the HCI-HAO board, which are
configurable by using HART SmartView, are listed in the following table.
Entity HART SmartView
Display
Data Type Type Default Function
[PV Link board ID]
PV linked Brd ID
Unsigned int
8 bits
Non-Volatile
<0>
Board
Specific
[PV Link board instance]
PV linked Brd IN
Unsigned int
8 bits
Non-Volatile <0>
[PV Link function instance]
PV linked Brd FI
Unsigned int
8 bits
Non-Volatile <0>
[PV Link Board Sensor Value]
PV link Brd SVAL
Enumeration Non-Volatile <PV_LINK>
[SV Link board ID]
SV linked Brd ID
Unsigned int
8 bits
Non-Volatile <0>
[SV Link board instance]
SV linked Brd IN
Unsigned int
8 bits
Non-Volatile <0>
[SV Link function instance]
SV linked Brd FI
Unsigned int
8 bits
Non-Volatile <0>
[Polling Address]
Polling Address
Unsigned int
8 bits
Non-Volatile <0> Communic
ation
[HART PV unit code]
PV Unit Code
Enumeration Non-Volatile <UNKNOW
N
[Upper Transducer Limit]
Upper Tran Limit
Float Non-Volatile <0>
[Lower Transducer Limit]
Lower Tran Limit
Float Non-Volatile <0>
[Transducer Serial Number]
Transducer Sr No
Unsigned int
32 bits
Non-Volatile <123>
[PV Lower range value]
Lw Range Value
Float Non-Volatile
<0>
Sensor
(Analog
Output)
[PV Upper range value]
Up Range Value
Float Non-Volatile <0>
[Analog Output mode]
HART Mode
Enumeration
<Fixed 4-
20mA>
<St
a
nd
a
r
d
4
-
Non-Volatile
<Standard
4-
20mA>
[Burnout Value]
Burnout Value
Float Non-Volatile
<3.6>
[Burnout Behavior]
Burnout Behavior
Enumeration
<BAD>
<UNCERTAI
N>
<BAD +
Non-Volatile <BAD>
[Enter Calibration Mode]
Enter Cal Mode
Undefined Command
[Cal Value at 4 mA]
Cal Value at 4 mA
Float Non-Volatile <0>
[Cal Value at 18 mA]
Cal Value at 18
Float Non-Volatile
<0>
[Calibrate at 4 mA]
Calibrate at 4 mA
Undefined Command
[Calibrate at 18 mA]
Calibrate at 18 mA
Undefined Command
[Exit Calibration Mode]
Exit Cal Mode
Undefined Command

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell FlexLine SmartServo 954 and is the answer not in the manual?

Honeywell FlexLine SmartServo 954 Specifications

General IconGeneral
BrandHoneywell
ModelFlexLine SmartServo 954
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals