COMMISSIONING
104 Service Manual Part No.: 4417340 Revision 1
954 SmartServo FlexLine
7.3.6.4.5 Not in Use
If an individual relay is not required in a particular application, the [Alarm
Mode] entity must be set to <Not In Use>.
Example: If a particular application requires only two relays to be used,
say relay 1 and 2, then for relay 3 and 4 the [Alarm Mode] entities must
be set to <Not In Use>.
☛
For the FII-DO relays not used within the application, set the [Alarm
Mode] entities to <Not In Use>.
7.3.6.5 Commands
The following commands can be given to the FII-DO:
Activate
Deactivate
Acknowledge
7.3.6.5.1 Activate
The !Activate! command will cause the specified relay to become
<Activated>. This command is only available in [Remote Control] mode;
see 7.3.6.4.4.
The !Activate! command behavior is modified by the [Time Setting]
entity. If the [Time Setting] entity is set to zero, the relay will stay
permanently activated until a !Deactivate! command is given.
If the [Time Setting] entity is set to a value other than zero, the relay will
be activated for a time in seconds equal to the value set in the [Time
Setting] entity, then deactivated. During the period the relay is activated,
the relay state will be !Time Setting Active!. This is useful for site
commissioning.
☛
For each relay, set the [Time Setting] entity to the desired value.
7.3.6.5.2 Deactivate
The !Deactivate! command will cause the specified relay to become
<Deactivated>. This command is only available in [Remote Control]
mode; see 7.3.6.4.4.