COMMISSIONING
Part No.: 4417340 Revision 1 Service Manual 169
954 SmartServo FlexLine
FlexConn interface address:
The address for FlexConn communication, ranging from 1900 till 1999.
Each SmartLink, connected to the same PC ComPort, must have a
unique address. Similar as with the GPU interface address, if changed
from default, also alter this FlexConn address at the SmartLink icon
(one level higher).
Password:
6 alpha-numerical characters. ChTRanging of some entities requires a
password. Default, ENRAF2 (or with newer software versions:
AAAAAA) is used as password. Unless it is changed in this entity; then
is requested for the password.
Parity:
Can be set to: Odd, Even or None. Standard Enraf GPU protocol (and
FlexConn protocol) uses Odd parity.
Modem control type:
The modern control type Can be:
- Isolated RS232 (uses connector CN2, marked 1 to 4)
- Isolated RS485 (uses connector CN3, marked 5 to 8)
- Non isolated RS232 (uses 9 pin D-type connector)
- Non isolated RS422 (uses 9 pin D-type connector)
- Non isolated RS232 (handshake) (uses 9 pin D-type
connector)
When
it is changed from default, make sure to adapt the
communication line according to the new setting.
ACK mechanism:
Can be set to Enable or Disable. When enabled, the SmartLink
transmits ACK characters about every 50 msec. after a host request is
received and the reply message is not yet ready.
Function identification:
In the SmartLink, the HCM-GPU module has the function of: GPU-slave
(the host is the GPU-master).