COMMISSIONING
102 Service Manual Part No.: 4417340 Revision 1
954 SmartServo FlexLine
☛
If [Local] [Monitor Mode] is to be set, skip to next bullet ().
☛
From the [Monitor Mode], select [Remote].
☛
Select [Remote Threshold Source], set desired value.
If the [Monitor Mode] is set to [Local], the scanned PV or SV
value is compared against the value set in the [Threshold]
entity. The behavior is modified by the [Threshold Mode]
and the [Hysteresis] entities. The [Threshold Mode] entity
can be set to either <Treat as HA> or <Treat as LA>.
If the [Threshold Mode] entity is set to <Treat as HA>, the
relay is activated if the scanned PV or SV is greater than or
equal to the [Threshold] entity value, and the relay is
deactivated if the scanned PV or SV is less than the
[Threshold] entity value minus the [Hysteresis] entity value.
If the [Threshold Mode] entity is set to <Treat as LA>, the
relay is activated if the scanned PV or SV is greater than or
equal to the [Threshold] entity value, and the relay is
deactivated if the scanned PV or SV is less than the
[Threshold] entity value plus the [Hysteresis] entity value.
☛
From the [Monitor Mode], select [Local].
☛
Select [Threshold Mode], and choose either <Treat as HA> or
<Treat as LA>.
☛
Select [Hysteresis], set desired value.
7.3.6.4.3 Status Behavior
The Status Behavior entity determines what happens to the relay if the
health of the scanned PV or SV differs from Good. The [Status
Behavior] should be set to one of the following options: <BAD>, <BAD-
UNCERTAIN>, or <Not Used>.
If the [Status Behavior] is set to <BAD>, and the scanned PV or SV
health is Bad, the respective relay will be activated.
If the [Status Behavior] is set to <BAD-UNCERTAIN>, and the scanned
PV or SV health is Bad or Uncertain, the respective relay will be
activated.