COMMISSIONING
Part No.: 4417340 Revision 1 Service Manual 89
954 SmartServo FlexLine
7.3.4.15 Maintenance
Name Value Range Default Value Explanation
[Wire tension
protection]
<enable>
<disable>
<enable> With this entity the possibility
exists to enable or disable the
wire tension high and low check.
If enabled a high or low fail code
will be generated if the tension
exceeds the low or high
thresholds.
[Drum slip
detection]
<enable> With this entity the possibility
exists to enable or disable the
drum slip detection. If enabled a
drum slip fail code will be
generated if the measured
frequency is below a certain
limit.
[Drum slip
occurrence]
Shows the number of drum slip
occurrences
[Motor position
errors]
Shows the number of observed
slip detections of the reference
encoder
[Set to
Maintenance mode]
This command resets the Servo
board and after that enters the
maintenance mode. In this mode
there are no level
measurements. Now the 4
frequencies can be measured or
the find reference encoder can
be done. A limited number of
commands can be issued.
[Operational mode] Shows the mode the gauge is in:
Operational or Maintenance
[Find reference
encoder position]
This command determines the
reference encoder position and
synchronizes this with position.
Only available in Maintenance
mode.
[Frequency 0]
[Frequency 1]
[Frequency 2]
[Frequency 3]
<0.0>
<0.0>
<0.0>
<0.0>
Frequency measured at resp.
25, 100, 175 and 250 g. load on
the wire.
[Measure
frequency]
This command will measure the
frequency with the actual
displacer/weight. The result is
placed in entity [Measured
frequency].