NO TE
Select Link smoke alarm with clasp lock open under Linkage Group. If its value is on, the
corresponding logic congurations under Linkage Logic List are available. If its value is o, the
corresponding logic
congurations under Linkage Logic List are unavailable.
Step 5 Modify the AI/DI_1 signal name.
1. Choose System Settings > Signal Name Modify. The Batch Signal
Conguration tab page is displayed.
2. Set Device type to ECC800, set Device name to ECC800, and click OK.
3. On the query result tab page, set the new signal name of AI/DI_1 to Smoke
and click Submit.
Step 6 Enable the AI/DI device.
1. Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_1
Port Settings.
2. Set Smoke sensor to Enable and click Submit.
3. Conrm that Smoke sensor type is automatically identied as Smoke sensor
or Smoke sensor(NC).
4. Click Unhide All Advanced Signals, and click Power Supply Parameters.
Ensure that III power supply enable(AIDI_1/DO) is Enable.
----End
Follow-up Procedure
After the smoke alarm is cleared, you need to manually close the door. After the
door is closed, the door open alarm is cleared.
5.3.10.2 Unlocking the Cabinet Electronic Clasp Lock When a Fire Alarm Is
Generated
Context
In this example, the
re extinguishing system connects to port AI/DI_3. The actual
port prevails.
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose System Settings > Linkage Control.
Step 3 Ensure that Enable linkage control function is Yes.
Step 4 On the Linkage Group tab page, set Link
re control with clasp lock open to
on.
NO TE
Select Link re control with clasp lock open under Linkage Group. If its value is on, the
corresponding logic congurations under Linkage Logic List are available. If its value is o, the
corresponding logic congurations under Linkage Logic List are unavailable.
FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S) 5 Power-On Commissioning
Issue 02 (2021-06-30) Copyright © Huawei Technologies Co., Ltd. 137

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule500 Smart and is the answer not in the manual?

Huawei FusionModule500 Smart Specifications

General IconGeneral
BrandHuawei
ModelFusionModule500 Smart
CategoryStorage
LanguageEnglish

Related product manuals