2.10.5 Changing the program execution type
(1) Changing the execution type using instructions
(a) Instructions used to change the execution type
The execution type of sequence programs can be changed using instructions even during execution.
Use the PSCAN, PSTOP, or POFF instruction to change the execution type.
Once the fixed scan execution type program is changed to another execution type, the type cannot be returned to the fixed
scan execution type.
Execution type before
change
Instruction
PSCAN PSTOP POFF
Scan execution type Remains unchanged. Changes to the stand-by type.
Turns off outputs in the next scan.
Changes to the stand-by type in two scans
later.
Initial execution type
Changes to the scan
execution type.
Changes to the stand-by type.
Turns off outputs in the next scan.
Changes to the stand-by type in two scans
later.
Stand-by type
Changes to the scan
execution type.
Remains unchanged. No processing
Fixed scan execution type
Changes to the scan
execution type.
Changes to the stand-by type.
Turns off outputs in the next scan.
Changes to the stand-by type in two scans
later.
Initial execution
type program
Stand-by type
program
Fixed scan execution
type program
Scan execution
type program
PSCAN
instruction
PSCAN
instruction
PSCAN
instruction
PSTOP, POFF
instruction
PSTOP, POFF
instruction
PSTOP, POFF
instruction

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric MELSEC-Q00U(J)CPU and is the answer not in the manual?

Mitsubishi Electric MELSEC-Q00U(J)CPU Specifications

General IconGeneral
BrandMitsubishi Electric
ModelMELSEC-Q00U(J)CPU
CategoryController
LanguageEnglish

Related product manuals