6 Parameters
6 - 22
E5@C-T Digital Temperature Controllers User’s Manual (H185)
rpt
Program Repetitions
link
Program Link Destination
• The Program Repetitions parameter is used to repeatedly execute the same program for
the specified number of repetitions. The actual number of executions will be the set value
of this parameter plus one.
• The Program Link Destination Number parameter sets the link destination for the
program. Operation will continue to the program with the number that is specified in this
parameter after execution of the current program is completed.
z Related Sections
5-15 Program-related Functions (page 5-53)
ts1s
Time Signal 1 Set Segment
Outputs must be assigned to time signals 1 and 2.
ts2s
Time Signal 2 Set Segment
• These parameters set the segment numbers that will use time signals.
• Up to two outputs can be set for each program. There is one timing setting for each
output.
z Related Sections
5-15 Program-related Functions (page 5-53)
z Related Parameters
Time Signal 1 and 2 ON Time and Time Signal 1 and 2 OFF Time (Program Setting
Level): Page 6-23
Control Output 1 and 2 Assignment (Advanced Function Setting Level): Page 6-97
Auxiliary Output 1 to 4 Assignment (Advanced Function Setting Level): Page 6-98
Function
Setting
Parameter Setting range Unit Default
Program Repetitions 0 to 9,999 Repetitions 0
Program Link Destination END or 0 to 7 --- END
See
See
Function
Setting
Setting range Unit Default
0 to 31 --- 0
See
See