4.7 Test Run with Load Connected
u
Test Run with the Load Connected
After performing a no-load test run connect the motor and proceed to run the motor and load together.
n
Notes on Connected Machinery
Clear the area around the motor.
The motor should come to a complete stop without problems.
Connect the machinery.
Fasten all installation screws properly. Check that the motor and connected machinery are held in place.
Confirm that the Fast-stop circuit or mechanical safety measures operate correctly.
Be ready to press the STOP button in case of emergency.
n
Checklist Before Operation
The motor should rotate in the proper direction.
The motor should accelerate and decelerate smoothly.
n
Operating the Motor under Loaded Conditions
Test run the application similarly to the no-load test procedure when connecting the machinery to the motor.
Check monitor parameter U1-03 to ensure there is no overcurrent.
If the application permits running the load in the reverse direction, try changing motor direction and the frequency
reference while watching for abnormal motor oscillation or vibration.
Correct any problems that occurs with hunting, oscillation, or other control-related issues.
4.7 Test Run with Load Connected
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
65
4
Start-Up Programming
& Operation

Table of Contents

Other manuals for Omron J1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron J1000 and is the answer not in the manual?

Omron J1000 Specifications

General IconGeneral
BrandOmron
ModelJ1000
CategoryInverter
LanguageEnglish

Related product manuals