7 PLC Setup
CP2E CPU Unit Software User’s Manual(W614)
7-2 PLC Setup Settings
7
7-2-5 Serial Option Port 2/Built-in RS-485 Port
The settings are applicable to the N30/40/60 CPU Units with Serial Option port 2, and the S30/40/60
CPU units with built-in RS-485 port.
Since this setting is reflected by power OFF and ON, the PLC Setup and the actual operation settings
may be different. The actual operation settings can be confirmed in words A618.
7-2-5 Serial Option Port 2/Built-in RS-485 Port
Communications Settings
Name Default Possible settings
When setting is read by
CPU Unit
1 Communications Settings Standard (9600;
1, 7, 2, E)
(Default settings)
Standard
Baud rate: 9,600 bps
Start bits: 1 bit
Data length: 7 bits
Parity: Even
Stop bits: 2 bits
When power is turned ON
Custom
2 Mode Host Link Host Link When power is turned ON
NT Link (1:N)
RS-232C (No-protocol)
PC Link (Slave)
PC Link (Master)
Modbus-RTU Easy Master
Modbus-RTU Slave
2-1 Host Link Settings
2-1-1 Baud 9,600 bps 1,200 bps When power is turned ON
2,400 bps
4,800 bps
9,600 bps
19,200 bps
38,400 bps
57,600 bps
115,200 bps
2-1-2 Format
(data length, stop bits, par-
ity)
7 bits, 2 bits, even 7 bits, 2 bits, even When power is turned ON
7 bits, 2 bits, odd
7 bits, 2 bits, no parity
7 bits, 1 bit, even
7 bits, 1 bit, odd
7 bits, 1 bit, no parity
8 bits, 2 bits, even
8 bits, 2 bits, odd
8 bits, 2 bits, no parity
8 bits, 1 bit, even
8 bits, 1 bit, odd
8 bits, 1 bit, no parity
2-1-3 Unit Number 0 0 When power is turned ON
:
31
2-2 NT Link (1:N) Settings
2-2-1 Baud 115,200 bps 38,400 bps (standard) When power is turned ON
115,200 bps (high speed)
2-2-2 No. NT/PC Link Max.
(Highest unit number of PT
that can be connected to
the PLC)
1 0 When power is turned ON
:
7