17-5
17 Analog Input/Output Option Board
CP2E CPU Unit Software User’s Manual(W614)
17-3 Installation and Setting
17
17-3-2 Setting
To use the analog option board on CP2E Nîš…îš…-type CPU Unit, it is necessary to set the serial commu-
nication settings in the PLC Settings.
Connect the CX-Programmer to the CPU Unit, and then change the PLC Settings as follows.
Serial Port Tab Page
Precautions for Correct UsePrecautions for Correct Use
When the Analog Option Board is applied on the CP2E CPU Unit, it is necessary to set the baud
rate to 115,200 and the mode to Host Link.
However, except the settings mentioned above, ERR LED will be lit if the communications is
impossible between the CPU Unit and the Analog Option Board. Check and change the settings.
Always turn OFF the power supply to the CPU unit and wait until all the operation indicators go out.
Press the up/down lock-levers on both sides of the Analog Option Board at the same time to unlock the
Option Board, and then pull it out.
17-3-2 Setting
Parameter Setting
Communications Settings Select the Custom option, set the baud rate to 115200 and the format to 7,2,E.
Mode Select Host Link (default) or Host Link.
Unit Number Select 0.
17-3-3 Removing