14 Serial Communications
14-12
CP2E CPU Unit Software User’s Manual(W614)
Built-in RS-232C, Built-in RS-485 or Serial Port Tab Page
Parameter Setting
Communications
Settings
Set the communications settings to the same values as the connected device.
If the connected device is set to 9,600 bps, two stop bits, and even parity, select the
Custom Option, set the baud rate to 9,600 and format to 7,2,E.
Mode Select RS-232C.
End Code • To specify the number of bytes of received data, select Received bytes and set the
number of bytes from 1 to 256.
• To use CR+LF as the end code, set CR+LF.
• To set the end code to any value between 00 to FF hex, set a value between
0x0000 and 0x00FF.
14-3-4 Related Auxiliary Area Bits and Words
Address Name Details
A392.04 Serial Port 1/Built-in RS-232C
Port Communications Error
Flag
ON when a communications error occurs at the serial port 1 or built-in
RS-232C port. The port must be restarted when this flag turns ON.
A392.05 Serial Port 1/Built-in RS-232C
Port Send Ready Flag
(No-protocol mode)
ON when the serial port 1 or built-in RS-232C port is able to send data
in no-protocol mode.
A392.06 Serial Port 1/Built-in RS-232C
Port Reception Completed
Flag
(No-protocol mode)
ON when the serial port 1 or built-in RS-232C port has completed the
reception in no-protocol mode.
• When the number of bytes was specified: ON when the specified
number of bytes is received.
• When the end code was specified: ON when the end code is received
or 256 bytes are received.
A392.07 Serial Port 1/Built-in RS-232C
Port Reception Overflow Flag
(No-protocol mode)
ON when a data overflow occurred during reception through the serial
port 1 or built-in RS-232C port in no-protocol mode.
• When the number of bytes was specified:
ON when more data is received after the reception was completed but
before RXD was executed.
• When the end code was specified:
ON when more data is received after the end code was received but
before RXD is executed.
ON when 257 bytes are received before the end code.
If a start code is specified, ON when the end code is received after
the start code is received.
A392.12 Serial Port 2/Built-in RS-485
Port Communications Error
Flag
ON when a communications error has occurred at the serial port 2 or
built-in RS-485 port. The port must be restarted when this flag turns
ON.
A392.13 Serial Port 2/Built-in RS-485
Port Send Ready Flag
(No-protocol Mode)
ON when the serial port 2 or built-in RS-485 port is able to send data in
no-protocol mode.
A392.14 Serial Port 2/Built-in RS-485
Port Reception Completed
Flag
(No-protocol Mode)
ON when the serial port 2 or built-in RS-485 port has completed the
reception in no-protocol mode.
• When the number of bytes was specified: ON when the specified
number of bytes is received.
• When the end code was specified: ON when the end code is received
or 256 bytes are received.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CP2E-E D Series and is the answer not in the manual?

Omron SYSMAC CP2E-E D Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CP2E-E D Series
CategoryComputer Hardware
LanguageEnglish

Related product manuals