15-59
15 Ethernet
CP2E CPU Unit Software User’s Manual(W614)
15-7 Status Allocations of Bulit-in Ethernet Port
15
15-7 Status Allocations of Bulit-in
Ethernet Port
The following table and descriptions cover the words and bits in the Auxiliary Area of PLC memory that
are related to the status of built-in Ethernet port.
Address Bit(s) Name Status Unit operation Access
A40 to A44 --- Ethernet Commu-
nication Error
Information
--- When an error occurs in Ethernet communi-
cation, the error information can be stored.
Refer to 6-1-11 Other Errors in the CP2E
CPU Unit Hardware User's Manual (Cat. No.
W613).
Read only
A45 14 Link Status (N20:
Ethernet port,
N30/40/60:
PORT1A)
ON Ethernet link is established. Read only
OFF Ethernet link is terminated.
15 Link Status
(N30/40/60:
PORT1B)
ON Ethernet link is established.
OFF Ethernet link is terminated.
A46 2 IP Address Set-
ting Error Flag
ON ON if any of the following conditions apply to
the IP address.
• All bits in the host ID are 0 or 1.
• All bits in the network ID are 0 or 1.
• All bits in the subnet ID are 1.
• The IP address begins with 127 (0x7F)
Read only
OFF OFF when the IP address is normal.
3 IP Address Table
Error Flag
ON ON if the IP address table information is
incorrect.
OFF OFF when the IP address table is normal.
4 IP Router Table
Error Flag
ON ON if the IP router table information is incor-
rect.
OFF OFF when the IP address table is normal.
5 DNS Server Error
Flag
ON ON when the following errors occur during
DNS server operation:
• An illegal server IP address is set.
• A timeout occurs during communications
with the server.
OFF OFF when DNS server operation is normal.
6 Routing Table
Error Flag
ON ON if the routing table information is incor-
rect.
OFF OFF when the routing table is normal.
11 SNTP Server Error ON ON when the following errors occur during
SNTP server operation:
• An illegal server IP address or host name is
set.
• A timeout occurs during communications
with the server.
OFF OFF when SNTP server operation is normal.
14 Address Disagree-
ment Flag
ON ON if the remote IP address is set to auto-
matic generation but the local IP address host
number and FINS node address do not agree
OFF OFF under all other circumstances
15 Ethernet Commu-
nication Error Flag
ON ON when Ethernet communication error
occurs.
OFF OFF when Ethernet communication error has
been cleared by Ethernet communication
error clear flag.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CP2E-E D Series and is the answer not in the manual?

Omron SYSMAC CP2E-E D Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CP2E-E D Series
CategoryComputer Hardware
LanguageEnglish

Related product manuals