17 Analog Input/Output Option Board
17-18
CP2E CPU Unit Software User’s Manual(W614)
z 0 to 10 V
The hexadecimal values 0000 to 0FA0 (0 to 4000) correspond to an analog voltage range of 0 to 10
V. The entire output range is 10 to 10.24 V.
Note When using current inputs, voltage input terminals must be short-circuited with current input terminals.
Analog Ouput Signal Ranges
Analog I/O Terminal Arrangement
0V
10V
0FA0
FFFF
0FFF
(4000) (4095)
0000(0)
Converted Data
Hexadecimal
(Decimal)
10.24V
VI1 Voltage Input 1
II1 Current Input 1
VI2
Voltage Input 2
II2 Current Input 2
COM Analog I/O Common
VO1 Voltage Output 1
VO2 Voltage Output 2
COM Analog I/O Common