Description
3.3 Technical features and system requirements for built-in motors
SIMOTICS M-1FE2 built-in motors
Hardware Installation Manual, 04/2020, A5E50074509B AA
43
Use a shared DC link.
Deactivate the displaced cycles.
are not observed, the motor can be damaged.
Recommendation:
Use the "SERVCOUP" OA software. This permits a simple design, a
simple commissioning and a better quality operation.
We recommend the use of an encoder switch / signal splitter from the following
manufacturers:
● DR. JOHANNES HEIDENHAIN GmbH
www.heidenhain.de
or
● BaumerHübner
www.baumer.com
3.3.4.3 Conversion of the converter setting data
As standard, the 1FE218☐ motor data always relates to the complete motor (both partial
windings) and is stored in the converter software. The values in the datasheets also refer to
the complete motor.
The values cannot be parameterized 1:1 for the master-slave operation. They must convert
the values to the individual subconverters.
The following example shows the conversion procedure.
Motor type: 1FE2184-8LH☐☐-☐CC0
V
motor
: 425 V