7 Web Main Interface User Manual
7.9.10 GOOSE
Configure the Data Logger to forward GOOSE services.
Before turning on this switch, ensure that the device is connected to a secure
network.
step 1 Click System > Transfer Configuration > GOOSE to enter the GOOSE page.
step 2 Set Switch to Enable.
step 3 Click Configuration File Export to export and save the GOOSE data configuration file locally.
step 4 Extract the exported package, and open the .cfg file using Excel in the package. View and modify
the GOOSE data configuration file.
step 5 Save the modified GOOSE data configuration file.
step 6 Click Configuration File Import on the operation bar, select the modified GOOSE data
configuration file, and click Open to import it.
- - End
7.9.11 Port Parameter
Configure serial ports of the Data Logger.
7.9.11.1 RS485
step 1 Click System > Port Parameter > RS485 to enter the RS485 page.
step 2 Click to modify Baud Rate, Parity Bit, Stop Bit, and PLC Access. The default value of
each parameter are as follows.
Parameter Default value
Port Function Collection
Baud Rate 9600
Parity Bit None
Stop Bit 1
PLC Access Disable
Fast Scheduling Switch Disable