User Manual 8 Grid Dispatching Function
Delete digital input manner: select a digital input manner that needs to be deleted, and click
Clear Data.
8.2.2.6 Country Mode
If the dispatching input must be the national power dispatching commands, set Reactive
Control Mode to Country Mode.
step 1 Click Power Control > Reactive Power to enter the Reactive Power page.
step 2 Set Reactive Control Mode to Country Mode.
step 3 Set Country and PPC Type, enter Forwarding Modbus ID, and click Save.
- - End
8.2.2.7 Disable Dispatching
Prohibit the Data Logger from performing reactive dispatching on the inverter.
step 1 Click Power Control > Reactive Power to enter the Reactive Power page.
step 2 Set Reactive Control Mode to Disable Dispatching, and click Save.
- - End
8.3 Emergency Button
To perform a batch shutdown for inverters, select Emergency Button.
Click Power Control > Emergency Button to enter the Emergency Button page.
Parameters Description
Emergency
Button
Enable: When the emergency stop switch is turned on, the
inverters will be collectively restored and powered on.
Disable: When the emergency stop switch is turned off, this
function remains inactive.
DI Port Associated with DI9~DI16 channel
Inverter
Status During
Emergency Stop
Recovery
Boot: When the emergency stop is deactivated, the inverters are
powered on in batch.
Shutdown: When the emergency stop is deactivated, the inverters
are in a powered-off state.
87