User Manual 8 Grid Dispatching Function
Parameters Description
Parameter Type
• When selecting Plant Parameter, set Plant Information and
PV Module Capacity further.
• When selecting Device Parameter, click Detailed Device
Parameter to view and set device information.
Time Calibration
Calibrate the time as needed. Calibration range: -10~10. When
the system time of Data Logger < the time adjusted after Time
Calibration, or the time of Data Logger < the NTP synchronized
time, Time Validity will be displayed as Invalid, at which time
Data Logger will send a stop command to the inverter, until Time
Calibration or NTP synchronization operation is performed.
When the country is set to China, the value for Scheduling Mode is set to DC Energy Storage
by default.
step 4 Click Save.
- - End
8.2.1.7 Disable Dispatching
Set Active Control Mode to Disable Dispatching to prohibit the Data Logger from
performing reactive dispatching on the inverter.
step 1 Click Power Control > Active Power to enter the Active Power page.
step 2 Set Active Control Mode to Disable Dispatching, and click Save.
- - End
8.2.2 Reactive Power
8.2.2.1 Disable Output
If the grid company does not need the power plant to adjust the voltage at the grid-
connection point, and the inverter does not need to cooperate with the grid for reactive
power compensation, the inverter keeps operating in the reactive-forbidden output state, and
the Reactive Control Mode is set to Disable Output.
step 1 Click Power Control > Reactive Power to enter the Reactive Power page.
step 2 Set Reactive Control Mode to Disable Output, and click Save.
- - End