wc_tx003610gb_FM10.fm
136
Mobile Generator
Using Remote Start Capabilities
13.4 Preparing for Automatic/Remote Start-Up (Deep Sea)
Background
In AUTO mode, the generator can be started remotely, either through a transfer
switch or some other type of remote start switch. AUTO mode is the normal setting
when using the generator as a stand-by power supply.
Procedure
1. Before putting using the AUTO mode,
perform a check of the auto start-up
circuit. To do so:
a.Attach a short jumper wire (a)
(minimum 16-gauge insulated)
between the two terminals on the
remote run terminal block. The
jumper wire applies a ground to the
ECM to complete the start circuit.
b.Set the genset controller power
switch (b) to the ON position.
c. Press the AUTO mode button (c).
d.Wait for the engine to crank, start,
and run. If the engine cranks, the remote start circuit is functioning.
e.Press the Stop/Reset “O” button (d) to stop the engine.
f. Remove the jumper wire from the remote run terminals after testing is
complete.
This procedure continues on the next page.
wc_gr011501
c
d
b
CAUTION
Possibility of accidental equipment start-up. If the contacts on any remote switch
linked to the generator are closed, the generator could start unexpectedly when the
AUTO mode button is pressed.
► Before pressing the AUTO mode button, verify that the contacts on any remote
switch linked to the generator are OPEN.
20A20A
50A50A
0 0 5 6 3 2
AUSAUS
APAGADOAPAGADO
ARRETARRET
OFFOFF
REMOTE STARTREMOTE START
FERNSTARTFERNSTART
ARRANQUE REMOTOARRANQUE REMOTO
DEMARRAGE A DEMARRAGE A
DISTANCEDISTANCE
START / LAUFENSTART / LAUFEN
ARRANQUE / MARCHAARRANQUE / MARCHA
DEMARRER / MARCHEDEMARRER / MARCHE
START / RUNSTART / RUN
a
wc_gr010206