Working with Basler Controller
8.8 Changing the Sender Fail Time Delays
Requirements
Machine stopped
Start switch in REMOTE START
Note: Internal programming of the genset controller or connections to a remote
start switch may cause the machine to start unexpectedly. Be prepared for the
engine to start even with the engine start switch in the REMOTE START position.
Background
There are five senders/sensors monitored by the genset controller. Each has its
own failure-time-delay period. This is the amount of time that the genset controller
must experience the failure before the failure will be seen on the LCD display.
These failure-time-delay periods may be changed. The table below lists the failure-
time-delay periods, the allowable range, and their factory settings.
Procedure
Perform the procedure below to change a fail time delay.
1. Press the right arrow button (1) to access the MAIN MENU.
This procedure continues on the next page.
Failure Time Delay Range Factory Setting
Coolant temperature sender 0 to 30 min 5 min
Oil pressure sender 0 to 300 sec 10 sec
Fuel level sender 0 to 300 sec 10 sec
Voltage sensor 0 to 300 sec 15 sec
Speed sender 0 to 300 sec 300 sec
wc_gr010134