Mobile Generator
Working with Basler Controller
8.16 Resetting a Loss of Voltage Pre-Alarm
Background
The loss of voltage pre-alarm condition occurs most often because of an open lug
door switch. During a loss of voltage pre-alarm, the LCD will display the screens
below.
To reset the loss of voltage pre-alarm, simply close the lug door. If the voltage does
not return to normal, further troubleshooting will be needed.
Note: The loss of voltage pre-alarm will only occur when the voltage selector
switch is in the 120/240 position. The condition will still exist if in a 3-phase mode,
but the pre-alarm will not activate.