wc_tx003229gb_FM10.fm
90
Mobile Generator
Working with Basler Controller
8.15 Resetting the Maintenance Interval Pre-Alarm
Requirements
Machine stopped
Start switch in REMOTE START
Note: Internal programming of the genset controller, or closed connections to a
remote start switch, may cause the machine to start unexpectedly. Be prepared for
the engine to start even with the engine start switch in the REMOTE START
position.
Background
When the MAINT INTERVAL pre-alarm is active, the PRE-ALARM ACTIVE screen
is displayed and the red LED flashes.
The maintenance interval pre-alarm may be reset by using either of two different
methods: 1) by holding the “X” reset button while the MAINT INTERVAL pre-alarm
screen is being displayed, or 2) through the METERING menu. Both methods are
described below.
Procedure
Perform the procedure below to reset the maintenance interval pre-alarm.
1. With the PRE-ALARM ACTIVE screen showing, press and hold the “X” reset
button (6) for 10–20 seconds. This will clear the pre-alarm and reset the
maintenance interval timer back to 250 (or the value it is currently set to).
If that method is unsuccessful, continue.
2. Press the right arrow button (1) to access the PRE-ALARMS menu.
This procedure continues on the next page.