wc_tx003229gb_FM10.fm
93
Mobile Generator Working with Basler Controller
8.17 Accessing and Using the Event Log
Requirements
Machine stopped
Start switch in REMOTE START
Note: Internal programming of the genset controller, or closed connections to a
remote start switch, may cause the machine to start unexpectedly. Be prepared for
the engine to start even with the engine start switch in the REMOTE START
position.
Background
The event log allows the technician to review recent events of the machine
including pre-alarm and alarm (shut-down) conditions. The event log can aid the
technician in diagnosing machine problems.
Note: Before accessing the event log, check the date and time of the genset
controller. The date and times listed in the event log will be relative to the date and
time setting of the genset controller.
Procedure
Perform the procedure below to access the event log.
1. At the READY screen, press the right arrow button to bring up the MAIN menu.
2. Highlight METERING. Then, press the right arrow button.
3. Highlight ALARMS-STATUS. Then, press the right arrow button.
4. Highlight EVENT LOG. Then, press the right arrow button.
The LCD displays the events of the event log. Events with the suffix “A” are alarm
conditions. Events with the suffix “P” are pre-alarm conditions. The events are:
LCD Screen Meaning
OVERCRANK A Overcrank pre-alarm
ENGINE RUNNING Engine running
PROT SHUTDOWN Protective shutdown
EMERGENCY STOP A Emergency stop alarm
ATS INPUT CLOSED Automatic transfer switch input closed
NORM SHUTDOWN Normal shutdown
FUEL LEVL SENDR FAIL P Fuel level sender failure pre-alarm
FUEL LEVL SENDR FAIL A Fuel level sender failure alarm
LOW FUEL LEVEL P Low fuel level pre-alarm
LOW FUEL LEVEL A Low fuel level alarm
OVER VOLTAGE P Over voltage pre-alarm
OVER CURRENT P Over current pre-alarm
LOW OIL PRES A Low oil pressure alarm
LOSS OF VOLT P Loss of voltage pre-alarm
LOSS OF VOLT Loss of voltage
LOW OIL PRES P Low oil pressure pre-alarm
LOW BATT VOLT P Low battery voltage pre-alarm
OIL SNDR FAIL P Oil sender failure pre-alarm
OIL SNDR FAIL Oil sender failure