Technical data 129
Electrical power network specification
A 115 - 230 V AC 3-phase power source (EN 61010 over-voltage category III or less)
is required. An AC power filter is required to comply with the CE directive for which
the MicroFlex e150 was tested (see CE marking on page 153).
* The MicroFlex e150 will operate at lower input voltages, although the drive will trip if
the DC-bus voltage falls below 50 V or 60% of the no-load voltage, whichever occurs
first.
Description Unit AC input
1Φ 3Φ
Nominal input voltage VAC 115 or 230
115 or 230
Minimum input voltage 105*
105*
Maximum input voltage 250
250
3A 6A 9A 3A 6A 9A
Nominal input current
@ maximum rated output current
A 7.515224 812
Nominal DC-bus voltage
@ 230 V AC input
305 321
Frequency 48 to 63 Hz, maximum rate of change 17%/s
Imbalance Max. ± 3% of nominal
phase to phase input
voltage
Fundamental power factor 0.98 (at nominal load)
Network type TN (grounded) systems.
Corner grounded TN, and IT (ungrounded)
systems not allowed.
Short circuit current protection
(UL 508C)
The drive is suitable for use on a circuit
capable of delivering not more than 5000 A
symmetrical amperes (rms) at 230 V
maximum when protected by fuses given in
the fuse table on page 136.

Table of Contents

Other manuals for ABB MicroFlex e150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB MicroFlex e150 and is the answer not in the manual?

ABB MicroFlex e150 Specifications

General IconGeneral
BrandABB
ModelMicroFlex e150
CategoryControl Unit
LanguageEnglish

Related product manuals