Technical data 157
UL marking
The MicroFlex e150 is C-UL US Listed only when used in conjunction with optional
Fan Tray (part FAN001-024, see page 164). The approval is valid with rated voltages.
When used without optional fan tray FAN001-024, the MicroFlex e150 is UL
Recognized.
UL checklist
• The drive is to be used in a heated, indoor controlled environment. The drive must
be installed in clean air according to enclosure classification. Cooling air must be
clean, free from corrosive materials and electrically conductive dust. See page
150.
• The maximum ambient air temperature is 45 °C (113 °F) at rated current. The
current is derated for 45 to 55 °C (113 to 131 °F).
• The drive is suitable for use in a circuit capable of delivering not more than
5,000 rms symmetrical amperes, 230 V maximum. The ampere rating is based on
tests done according to UL 508C.
• The cables located within the motor circuit must be rated for at least 75 °C
(167 °F) in UL-compliant installations.
• Use copper conductors only.
• The input cable must be protected with fuses. Circuit breakers must not be used
without fuses in the USA. Page 136 lists IEC fuses that are suitable for UL
applications. For suitable circuit breakers, contact your local ABB representative.
• For installation in the United States, branch circuit protection must be provided in
accordance with the National Electrical Code (NEC) and any applicable local
codes. To fulfill this requirement, use the UL classified fuses.
• For installation in Canada, branch circuit protection must be provided in
accordance with the Canadian Electrical Code and any applicable provincial
codes. To fulfill this requirement, use the UL classified fuses.
• The drive provides overload protection in accordance with the National Electrical
Code (NEC).