USING THE CLP INTERFACE
EATON Managed ePDUt User’s Guide S 164201xxx Rev 1 DRAFT 10−OCT−2008
93
Figure 96 shows an example of the output when the show command is entered with
the name attribute.
Figure 96. Example 2 – Name Attribute
Figure 97 shows an example of the output when the show command is entered with
the powerState attribute.
Figure 97. Example 3 – powerState Attribute
Turning an Outlet On or Off
The set command turns an outlet on or off.
Syntax
The following is the syntax for the set command:
clp:/> set /system1/outlet powerState=on|off
where the keyword on turns the outlet on and the keyword off turns the outlet off.
Querying an Outlet Sensor
The show command with the Antecedent key word queries the outlet sensors
clp:/−> Show –d properties=Antecedent system1/<outlet number>=>
AssociatedSensor
where <outlet number> is the number of the outlet.