USING THE IPMI TOOL SET
EATON Managed ePDUt User’s Guide S 164201xxx Rev 1 DRAFT 10−OCT−2008
103
Get Group Membership Command
Request Data 1 Group number
[7–5] reserved
[4–0] group number, valid numbers: 0–23
Response Data
1 Completion Code
2 [7–1] reserved
[0] 1b = group is enabled, 0b = group is disabled
3 [7] 1b = socket 7 belongs to group
[0] 1b = socket 0 belongs to group
4 [7] 1b = socket 15 belongs to group
[0] 1b = socket 8 belongs to group
5 [7] 1b = socket 23 belongs to group
[0] 1b = socket 16 belongs to group
Set Group Power On Delay Command
Request Data
1 Group number
[7–5] reserved
[4–0] group number, valid numbers: 0–23
2 Delay in 1/10 seconds
This delay overwrites the global delay for all of the sockets in that group.
The delay applies not only when using the Set Group State command, but
also when using the Set Receptacle State command.
Response Data 1 Completion Code
Get Group Power On Delay Command
Request Data 1 Group number
[7–5] reserved
[4–0] group number, valid numbers: 0–23
Response Data
1 Completion Code
2 Delay in 1/10 seconds

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Managed ePDU and is the answer not in the manual?

Eaton Managed ePDU Specifications

General IconGeneral
BrandEaton
ModelManaged ePDU
CategoryPower distribution unit
LanguageEnglish

Related product manuals