FloBoss 107 Instruction Manual
2-2 Installation and Use Revised June-2017
Note: In salt spray environments, it is especially important to ensure that
the enclosure, including all entry and exit points, is sealed
properly.
The FB107 is designed to operate over a 40 to 75°C (40 to 167°F)
temperature range. When mounting the unit, be aware of external devices
that could have an effect on the operating temperature. Operation beyond
the recommended temperature range could cause errors and erratic
performance. Prolonged operation under extreme conditions could also
result in failure of the unit.
The FB107 is designed to function in 90% or less non-condensing
humidity.
2.1.2 Site Requirements
Careful consideration in locating the FB107 on the site can help prevent
future operational problems. Consider the following when choosing a
location:
Follow all local, state, and federal codes regarding monitoring
locations and site requirements. Examples of these restrictions are
distance from pipe flanges and hazardous area classifications.
Locate the FB107 to minimize the length of signal and power wiring.
Locate antennas for radio and cellular communications with an
unobstructed signal path. If possible, locate antennas at the highest
point on the site and avoid aiming antennas into storage tanks,
buildings, or other tall structures. Allow sufficient overhead clearance
to raise the antenna.
Minimize interference with radio or cellular communications by
locating the FB107 away from electrical noise sources, such as
engines, large electric motors, and utility line transformers.
Locate the FB107 away from heavy traffic areas to reduce the risk of
being damaged by vehicles. However, provide adequate vehicle
access to aid in monitoring and maintenance.
Consider the physical dimensions of the FB107 (see Figures 2-1 and
2-2):
Base: 196 mm H by 158 mm W by 134 mm D (7.72 in. H by 6.22
in. W by 5.29 in. D).
Base plus expansion rack: 196 mm H by 317 mm W by 134 mm
D (7.72 in. H by 12.48 in. W by 5.29 in. D).

Table of Contents

Other manuals for Emerson FloBoss 107

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson FloBoss 107 and is the answer not in the manual?

Emerson FloBoss 107 Specifications

General IconGeneral
BrandEmerson
ModelFloBoss 107
CategoryController
LanguageEnglish

Related product manuals