Chapter 3: Programming
EST iO64 and iO500 Technical Reference Manual 147
Panel operation programming
The panel operation options include the panel language,
marketplace, AC fail delay, zone resound, reset inhibit, auto signal
silence, day start, night start, daylight savings, date format,
mapping, and the LCD banner. These options control how the panel
operates. Each option has settings that can be programmed. Most
options also have a factory default setting, which can be used with
no additional programming. See "Factory Default Settings" for more
information.
Panel operation programming options
Language Select the desired display language: English or French
Marketplace Select the desired marketplace: U.S. or Canada
AC fail delay Set the AC fail delay time to:
Off: Off-premises notification of an AC power failure is immediate. Note: The "off" setting is not
acceptable for UL/ULC installations. Refer to "UL 864 programming requirements" for details.
1 to 15 hours: Delays the off-premises notification of an AC power failure by the time period
selected
Zone resound Set zone resound to:
On: NACs resound each time a device in the zone goes into alarm even if they were silenced
Off: Inhibits the NACs from turning on again (after they were silenced) when a second device in
the zone goes into alarm. Note: The "off" setting is not acceptable for UL/ULC installations. Refer
to "UL 864 programming requirements" for details.
Reset inhibit Set the time to:
Off: Panel reset is operational immediately after NACs turn on
1 minute: Panel reset is operational one minute after NACs turn on
Auto signal silence Set auto signal silence to:
Off: Does not allow the panel to automatically silence the signals
5 to 30 minutes: Allows the panel to automatically silence the signals after the selected time
period expires
Day start Set the start time for daytime sensitivity
Night start Set the start time for nighttime sensitivity
Date Set the date format to:
U.S.: MM/DD/YYYY
Canada: DD/MM/YYYY
LCD banner Enter your desired banner text for line one and line two using the keypad. Each line is capable
of up to 20 characters. Select Save when finished.
Aux power reset On: Reset temporarily turns off the resettable aux power output
Off: Reset does not turn off the resettable aux power output
Event notification Set event notification to:
Zone: When a device is a member of a zone
onl
the zone information is sent to the LCD