10. OTHER FUNCTIONS
10.6.3 Remote PAUSE
Remote PAUSE refers to the function that performs PAUSE function to the QnACPU from
an external source while the CPU module RUN/STOP key switch is set to the RUN
position.
The PAUSE function stops a CPU module operation while retaining the ON/OFF status of
all outputs (Y).
(1) Application of remote PAUSE
This function can be used to retain the output (Y) with ON status even if the CPU
module is in STOP due to process control.
(2) Methods for remote PAUSE
The following two methods are available for performing remote PAUSE.
(a) Method using a remote PAUSE contact
The remote PAUSE contact is set in the PLC system in the parameter mode of
GPP function.
The settable device range is from input X0 to 1FFF.
1) When the scan END processing is performed with both the remote PAUSE
contact and the PAUSE enable flag (SM206) are ON, the PAUSE status
contact (SM204) turns ON.
When performing up to the END instruction of the scan following the scan in
which the PAUSE status contact turned ON, the PAUSE state is established
and operation is stopped.
2) When turning the remote PAUSE contact OFF or turning SM206 OFF with
GPP function, the PAUSE status is reset and the sequence program
operation is again performed from step 0.
REMARK
When the remote RUN contact is made same as the remote PAUSE contact, the
remote PAUSE contact will be invalid.
Fig. 10.6 Time chart for PAUSE with remote PAUSE contact
OFF
ON
0 END
0 END 0 0
END END
SM206
OFF
ON
SM204
OFF
ON
RUN
PAUSE
Remote PAUSE
contact
RUN/PAUSE
status
ON when PAUSE
condition is satisfied
PAUSE status