HARDWARE SPECIFICATIONS OF CPU MODULES
15 HARDWARE SPECIFICATIONS OF CPU MODULES
15.1 SPECIFICATIONS
The general specification common to various modules is shown.
*1 This indicates that the equipment is assumed to be connected to which power distributer in
the area from the public electrical power distribution network to machinery in the premises.
Category II applies to equipment to which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300V is 2500V.
*2 This index indicates the degree of conductive material generation in the environment where
the equipment is used.
In Pollution degree 2, only non-conductive pollution occurs. Occasionally, however, temporary
conductivity caused by condensation can be expected.
*3 Do not use or store the PLC in the environment where the pressure is higher than the
atmospheric pressure at sea level. Otherwise, malfunction may result.
To use the PLC in high-pressure environment, please contact your local Mitsubishi
representative.
Specifications
Item Specifications
Operating ambient
temperature
0 to 55
Storage ambient
temperature
-20 to 75
Operating ambient humidity 10 to 90 % RH, No-condensing
Storage ambient humidity 10 to 90 % RH, No-condensing
Vibration resistance
Conforming to
JIS B 3502,
IEC 61131-2
Frequency Acceleration Amplitude Sweep count
Under
intermittent
vibration
10 to 57Hz –
0.075mm
(0.003 inch)
10 times each
in X, Y, Z
directions
57 to 150Hz
9.8m/s
2
–
Under
continuous
vibration
10 to 57Hz –
0.035mm
(0.001inch)
–
57 to 150Hz
4.9m/s
2
–
Shock resistance
Conforming to JIS B 3502, IEC 61131-2 (147m/s
2
, 3 times in each of 3 directions XYZ)
Operation ambiance No corrosive gasses
Operating elevation
*3
2000m (6562 ft.) or less
Installation location Control panel
Overvoltage category
*1
II or lower
Pollution degree
*2
2 or lower
Equipment category Class I