Rotate Every
Selects rotation period. Valid values:
• 12 hrs
• 24 hrs
Rotate Now
Immediately performs rotation.
Rotation Frequency
Frequency at which rotation occurs. Options include:
• No: Rotation disabled.
• Daily: Rotation occurs every day.
• Every [Day of Week]: Rotation occurs weekly on the same day.
• Monthly [Day of Week]: Rotation occurs monthly on the same day.
6.4.2 Manually Rotating the Operating and Standby Units
You can rotate the operating and standby units outside of the set schedule using Rotate Now.
NOTE: Manual rotation may only be performed at the cooling unit designated as the lead unit, “U2UAddress=1,” of
the group.
NOTE: The Rotate Now button may only be available when a Rotation Frequency is selected. See Setting a Rotation
Schedule on the previous page .
1. At the cooling unit, verify that it is the lead unit of the group:
• Touch , then > BMS & Teamwork Setup > U2U Setup.
• In the CONTROL BOARD column, verify that the U2U Address is 1.
If it is the lead unit, continue with step 2 .
If it is not the lead unit, find the lead unit and start at step 1 .
2. Touch , then > BMS & Teamwork Setup > Teamwork / Standby. The TEAMWORK/STANDBY panel
opens.
3. Touch Unit Rotation. The UNIT ROTATION CONTROL panel displays.
4. Touch Rotate Now, then touch Save. The operating and standby units are rotated.
6 Teamwork, Standby and RotationforCoolingUnits
108
Vertiv™ Liebert® iCOM™Installer/User Guide