8.2.9 Velocity Protocol Configuration
Velocity protocol contains four sub-folders: Managed Device, MSTP, Ethernet, and Internal.
NOTE: With the exception of changing the node ID when multiple cards are used or when disabling Velocity Protocol
IP access, the settings in the Velocity Protocol sub-folders should not be modified unless directed by a Vertiv™
representative.
1. Touch , then > BMS & Teamwork > IS-Unity
Setup > Configuration > Velocity Protocol.
2. Adjust the settings, and touch Save.
Velocity Protocol Options
Velocity Protocol IP Access
When disabled, prevents access from a remote, IP-based system using the Velocity Protocol.
Velocity Protocol Managed Device Options
Connection State
Status of connection to managed device.
FDM Version
Version of the managed device.
Product Sequence ID
Product sequence identifier of the managed device.
LAN Type
Type of interface connection to the managed device. Must be set to MSTP Internal for correct communication with
Vertiv™ Liebert® iCOM™.
Node ID(MSTP Only)
Identifier of the managed device on an MSTP LAN.
IP Address (IPOnly)
Address of the managed device on an IPLAN.
Velocity Protocol MSTP Options
Interface
Type of MSTP interface.
Data Rate
Communication rate in bps.
8 External Monitoring andBuilding ManagementSystems
135
Vertiv™ Liebert® iCOM™Installer/User Guide

Table of Contents

Other manuals for Vertiv Liebert iCOM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Liebert iCOM and is the answer not in the manual?

Vertiv Liebert iCOM Specifications

General IconGeneral
BrandVertiv
ModelLiebert iCOM
CategoryControl Unit
LanguageEnglish

Related product manuals