4.3 Selecting Event Type and SettingAlarm/WarningNotification
Setting notification delays and disabling visual notification prevents nuisance notifications. Customize to notify of critical
events on your cooling system.
NOTE: If the event includes a safety function, such as high pressure, low pressure, main fan overload, etc., the safety
function executes regardless of event type or notification setting. However, notification timing delays still apply.
Table 4.2 on page87 , lists the default and adjustable notification settings for events. Table 4.3 on page88 , describes
evens for the Vertiv™ Liebert® MCCondenser. Table 4.4 on page90 , describes events for the Vertiv™ Liebert® EconoPhase
unit. Table 4.5 on page91 , describes events for the Vertiv™ Liebert® DSE compressors. Table 4.6 on page91 , describes
events for the EEValarm board.
To select event type and notification:
1. Touch , then > Alarm/Event Setup.
2. Scroll or search to find the event and touch the alarm or event.
3. On the EDIT panel, touch Notifications. The EDIT panel displays the notification properties.
4. Adjust the notification properties described in the Notification Properties below , then touch Save. The
notification is updated.
• Touch Cancel to discard the changes without saving.
4.3.1 Notification Properties
Delay
Time, in seconds, to delay notification after event trigger. Depending on the event, the delay may or may not be
adjusted. Table 4.2 on page87 , lists the delays and their default settings.
• If the notification delay for the event is greater than the delay set for the event group, the group’s delay includes
the event’s delay.
4 Managing Events: Alarms,WarningsandMessages
83
Vertiv™ Liebert® iCOM™Installer/User Guide