2.2.2 Alarm Detail Fields
Alarm
Name of the event.
Alarm Type
Number representing the event type.
1 : Warning
2: Alarm
Date/Time
Date and time the event was logged.
Duration
Time elapsed since event was logged.
Threshold
Sensor reading at which an event is triggered.
Unit
Cooling unit to which the alarm applies.
Value
The current value to which the threshold is compared.
2.2.3 Silencing an Audible Alarm
Touch the screen to silence an audible alarm. If the alarm is non-latching, the alarm silences when the condition clears.
NOTE: The audible alarm must be enabled in display options to sound. See Enabling the Audible Alarm Notification on
page92 .
2.2.4 Acknowledging Alarms
Depending on the notification settings, alarms and warnings must be acknowledged or reset. An event is active as long as it is
unacknowledged, with the exception of the network failure events described in Table 2.2 on the facing page . Once
acknowledged, an event remains active until the situation that triggered the event is resolved, see Table 2.1 on the previous
page , for event status indicators. When an event acknowledged and cleared, it is removed from the Alarms panel and the LED
stops flashing red.
NOTE: Acknowledging alarm events does not clear them. To clear an issue, it must be corrected, reset automatically
by the controller, or reset manually.
2 User Operation
18
Vertiv™ Liebert® iCOM™Installer/User Guide

Table of Contents

Other manuals for Vertiv Liebert iCOM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Liebert iCOM and is the answer not in the manual?

Vertiv Liebert iCOM Specifications

General IconGeneral
BrandVertiv
ModelLiebert iCOM
CategoryControl Unit
LanguageEnglish

Related product manuals