11.12 Diagnosing Water Leak Detection Issues
1. Touch , then > Diagnostic/Service > Diagnostics > Water Detection in the Category list. The WATER
DETECTION panel displays.
2. Refer to Diagnostics—Water Leak Detection Options below , for descriptions of diagnostic options.
NOTE: Depending on the type of thermal management unit, included components, and control settings of your system,
all of the options listed may not be available on your Vertiv™ Liebert® iCOM™ display.
11.12.1 Diagnostics—Water Leak Detection Options
LWD Value
Current percentage of resistance measured from the leakage water detection sensor. See Setting Water Leak Detector
Options on page67 . Range of values across:
• 0%: Maximum resistance, sensor is dry.
• 100%:Minimum resistance, sensor is wet.
11 Performing Diagnostics
174