2. Select IntelliSlot Card Settings and one of the following in Monitoring Protocol:
• Embedded to use built-in Unity function.
• Embedded & IS V4 to use built-in Unity and additional IntelliSlot™ card or SiteLink connection.
3. Touch Save & Restart (Unit Only).
IntelliSlot Options
Monitoring Address
Address used by an optional, installed IntelliSlot™ card. Factory default is 3.
• Do not modify the monitoring address unless directed to do so by Vertiv technical support.
Monitoring Protocol
Protocol used for communication with BMS. Options are:
• Velocity V3: Legacy Velocity communication card.
• IGM: IGMNet communication cards.
• Velocity V4: IntelliSlot™ Card or Sitelink/Sitescan™. This is the factory default.
• Embedded: Embedded IS-UNITY function.
• Embedded and IS V4: To use built-in Unity and an additional IntelliSlot card or SiteLink/Sitescan connection.
NOTE: If a Sitelink/Sitescan Connection and MODBUS RTU or BACnet MSTP RS-485 connection is required
simultaneously, then the purchase of the RS-485 expansion board is required.
8.1.2 Setting BMS Control Settings
1. Touch , then > BMS & Teamwork > BMS Setup > Control Settings. The CONTROL SETTINGS
secondary panel opens.
2. Adjust the settings, and touch Save. The settings are configured.
NOTE: Use Configure Timeout to configure the setpoints used in the event of an outage and BMS takes control. See
Setting BMS Backup Setpoints on the facing page .
NOTE: Depending on the type of thermal management unit, included components, and control settings of your system,
all of the options listed may not be available on your Vertiv™ Liebert® iCOM™ display.
BMS Control Settings Options
BMS is Connected To
• Velocity
• Analog Input 1-4
BMS Fan Speed Local Override
Enables/disables local override of the fan-speed set via BMS.
8 External Monitoring andBuilding ManagementSystems
118
Vertiv™ Liebert® iCOM™Installer/User Guide