EasyManuals Logo
Home>Wintriss>Controller>wpc 2000

Wintriss wpc 2000 User Manual

Wintriss wpc 2000
250 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #108 background imageLoading...
Page #108 background image
WPC 2000 User Manual 1128500
Initialization, Setup, and Checkout 3-17
4. When the value you want is shown in the LED display, save your setting by pressing the
Reset/Select button until the “Angle/SPM” indicator is lit.
5. Set option switch 7 to ON to disable changes to the Stop-time Limit (see step 1).
6. Power down WPC 2000, then power the unit back up to enable the new setting.
Determining the 90° Stop Time
The 90° stop-time test is required to set the proper safety distance for personnel guarding
devices including light curtains, Two-hand controls, and type-B movable barriers. The test is
performed at the press’s most critical stopping point– 90°– and provides the Ts + Tc value in
the ANSI safety distance formula. If possible, run this test in Continuous mode (see next
section). If your press does not have a Continuous setting, perform the test in Single-stroke as
instructed in Performing the 90° Stop Test (Single-stroke Mode), page 3-18.
Performing the 90° Stop Test (Continuous Mode)
1. Install the heaviest upper die in your press. Adjust the counterbalance for ram weight, if
your press has a counterbalance.
2. Set the Stroke Select switch to “CONT,” and start the press.
3. Press the Reset/Select button repeatedly until the “90° Stop Test” indicator becomes lit
(see Figure 3-8).
INCORRECT SAFETY DISTANCE DUE TO INCORRECT STOP TIME
Perform a 90° Stop Test any time you change the Stop-time Limit of WPC 2000.
Recalculate the safety distance based on the new Stop-time Limit and adjust or reinstall
safeguarding devices according to the new safety distance (see Calculating the Safety
Distance, page 3-19).
Failure to comply with these instructions will result in death or serious injury.
Figure 3-8. WPC 2000 Display Showing Results of 90° Stop-time Test
DANGER
!
With 90° Stop Test segment
selected, turn WPC Settings
key switch to + to arm the
test. Segment flashes when
test is armed. Results
appear in LED display
when test is complete.
BRAKE WARNING
INTERRUPTED STROKE
TOP STOP ANGLE
AUTO CARRYUP
STOP TIME LIMIT
MICRO-INCH
STOPPING TIME
STOPPING ANGLE
90
° STOP TEST
COUNTER
COUNTER PRESET
ANGLE / SPM
cam on angle cam off angle

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Wintriss wpc 2000 and is the answer not in the manual?

Wintriss wpc 2000 Specifications

General IconGeneral
BrandWintriss
Modelwpc 2000
CategoryController
LanguageEnglish

Related product manuals