Tripping logic
ABB Network Partner AB
1MRK 580 120-XEN
Page 5 - 3
Version 1.0-00
Signal To phase...
L1TRIP L1
L2TRIP L2
L3TRIP L3
External tripping signals can also cause a single-phase tripping without
any restriction.
Fig. 2 Single-phase front logic—simplified logic diagram
You can configure the TRIP-TRSPE signal to the output signal of the EF-
--TREF overcurrent, earth-fault, protection function (directional and non-
directional). This enables single-phase tripping when the faulty phase is
detected by some other phase-selection element such as the phase selec-
tion in distance protection.
2.3 Tripping logic circuits Fig. 3 shows a simplified illustration of the tripping logic circuits. The
TRIP-BLOCK signal might block the operation of the complete tripping
unit. In a similar way, an external TRIP-EXTTRIP signal can cause
instantaneous three-phase tripping if the function has not been blocked by
external signal or the terminal has been switched to operational testing
mode with activated blocking. A functional TRIP-PTPTRIP input signal
prepares the three-phase tripping conditions for any of the tripping signals
arriving from the front logics. Timers, delayed for 2 seconds at drop-out,
assure correct three-phase tripping for evolving faults.
TRIP-TRTP
TRIP-EXTL1
TRIP-PSL1
TRIP-EXTL2
TRIP-PSL2
1
V
1
V
1
V
L1TRIP
L2TRIP
L3TRIP
To
Fig 3
TRIP-EXTL3
TRIP-PSL3
TRIP-TRSPE
TRIP-TRSPZ
t
50ms
Loop delay
&
&
1
V
&
&
&
&
Loop delay
1
V
&
1
V
1
V
1
V
1
V
(X80120-2)