6 Technical data
Table 1: Energizing quantities, rated values and limits
Quantity Rated value Nominal range
Current
Operative range
Burden
I
r
= 1 or 5 A
(0,2-4) × I
r
cont.
(0,2-100) × I
r
for 1 s
*)
< 0,25 VA at I
r
(0,2-30) x I
r
Ac voltage Ph-Ph
Operative range
Burden
U
r
= 100/110/115/120 V
1,5 × U
r
cont.
2,5 × U
r
for 1 s
< 0,2 VA at U
r
(80-120) % of U
r
Frequency f
r
= 50/60 Hz ± 5 %
Auxiliary dc voltage EL
power consumption
basic terminal
U
r
= (48-250) V
≤ 16 W
± 20 %
Binary input(8)/output(12) module
dc voltage RL
power consumption
each I/O-board
each output relay
RL24 = (24/30)V
RL48 = (48/60)V
RL110 = (110/125)V
RL220 = (220/250)V
RL24 = (24/30)V
RL48 = (48/60)V
RL110 = (110/125)V
RL220 = (220/250)V
≤ 1 W
≤ 0,15 W
max. 0,05 W/input
max. 0,1 W/input
max. 0,2 W/input
max. 0,4 W/input
± 20 %
± 20 %
± 20 %
± 20 %
Binary input module
dc voltage RL
power consumption
each input-board
RL24 = (24/30)V
RL48 = (48/60)V
RL110 = (110/125)V
RL220 = (220/250)V
RL24 = (24/30)V
RL48 = (48/60)V
RL110 = (110/125)V
RL220 = (220/250)V
≤ 0,5 W
max. 0,05 W/input
max. 0,1 W/input
max. 0,2 W/input
max. 0,4 W/input
± 20 %
± 20 %
± 20 %
± 20 %
Binary output module
power consumption
each output-board
each output relay
≤ 1,0 W
≤ 0,25 W
mA input module
input range
input resistance
power consumption
each mA-board
each mA input
± 5, ± 10, ± 20 mA
0-5, 0-10, 0-20, 4-20 mA
R
in
= 194 Ohm
≤ 4 W
≤ 0,1 W
± 10 %
Ambient temperature 20° C-5° C to +55° C
Ripple in dc auxiliary voltage max. 2 % max. 12 %
Relative humidity (10-90) % (10-90) %
*) max. 350 A for 1 s when COMBIFLEX test switch included together with the product