ABB Network Partner AB
Menu tree REC 561
Version 1.0-00
1MRK 580 189-XEN
Page 3 - 40
4 Settings
Use this menu to set different parameters within the built-in functions.
4.1 Functions You can set different setting parameters for basic and optional protection
and automation functions that are built into the terminal. The parameters
are independent of each other, within four separate setting groups.
4.2 Changing of an active
setting group
Users can select the active setting group in a dialogue window, using a
command with confirmation.
4.3 Disturbance report You can set these parameters from the Disturbance report submenu:
• On or Off, which specifies if the disturbance reporting unit is acti-
vated or deactivated.
• Recording times, for example, pre-fault, post-fault, and limit time.
• Triggering functions.
• Masking - to enable man machine communication of up to 48 binary
signals that are selected when configuring the terminal.
• Up to 10 analogue signals that are recorded by the disturbance
recorder (when they are included in the terminal).
• Triggering mode (overfunction, underfunction, and Off-mode, as
necessary).
4.4 Internal time Use this submenu to set and read the internal time (year, month, day, hour,
minute, second) of a terminal.
5 Terminal status
This menu displays some of the most important information on the termi-
nal. This information consists of:
• Self supervision - report
• ID of the terminal
5.1 Self supervision -
report
The terminals of the REx 5xx series have built-in extensive self-supervi-
sion functions, which inform the user about errors detected in the termi-
nal.
If an error occurs in the terminal, a general warning signal appears,
together with information about the faulty module in the terminal. In addi-
tion, a self-supervision function also displays the status of time synchroni-
zation.