Tripping logic
Version 1.0-00
1MRK 580 120-XEN
Page 5 - 8
4.3 Setting table
TRIP-PSL3 Necessary condition for single phase trip in phase L3. Generally connected to protective
functions with phase selective operation
TRIP-PTPTRIP Turns the tripping logic into three phase operating mode.
TRIP-TRSPZ Initiation of single phase tripping. Requires a phase selection signal. In opposite case initi-
ate 50 ms delayed three phase tripping.
TRIP-TRTP Initiation of three phase tripping.
OUT: DESCRIPTION:
TRIP-GTRIP General information on tripping caused by tripping logic within the terminal.
TRIP-SPTRIP General information on single phase tripping caused by tripping logic within the terminal
TRIP-TPTRIP General information on three phase tripping caused by tripping logic within the terminal
TRIP-TRIPL1 Trip in phase L1
TRIP-TRIPL2 Trip in phase L2
TRIP-TRIPL3 Trip in phase L3
IN: DESCRIPTION:
PARAMETER: SETTING RANGE: DESCRIPTION
Operation Off, 3ph, 1ph Operating mode of the tripping logic.
Off: the operation is disabled.
3ph: only three phase tripping is possible.
1ph: single phase or three phase tripping, dependent on combina-
tion of different input signals