ABB Network Partner AB
Menu tree REC 561
Version 1.0-00
1MRK 580 189-XEN
Page 3 - 42
6.5 Built-in man machine
interface (MMI)
You can activate the setting restriction function, which restricts the
changes of setting values and active groups via the built-in MMI.
6.6 SPA communication Parameters for SPA communication must be specified for each communi-
cation port (one on the rear plane (optional) and one in the front). You can
select the communication speed for each communication channel sepa-
rately. For the two rear channels (one SPA and one LON) you can set the
access level to the terminal.
6.7 LON communication For the LON communication, you can read node information as address
and location, which are set from the LON Network Tool and also read the
Neuron ID. At installation of a node, you can enter a ServicePinMsg com-
mand to define for the terminal the address that is set in the LON Network
Tool. You can also reset all LON configurations by giving the command
LONDefault.
7 Command
Under the command menu, you can activate different output signals for
performance of various commands in the terminal. From the CAP 531
configuration tool, you can assign the commands with a programmable
name.
8Test
Use this menu for testing purposes - to make secondary injection testing
of the terminal as easy as possible. The user can block all binary outputs
to prevent unwanted tripping of the circuit breaker and to prevent the
sending of alarm signals to the control room and the control centre during
the testing activities.
Under the block function menu, functions can be On or Off during testing.
Similarly, you can block the operation of the disturbance report so as not
to overload the memory with operations caused by the secondary injection
testing. Automatic testing logic can be used under this submenu.
You can set the terminal in configuration mode, which stops the execution
of the logical functions, when the configuration is down-loaded from the
CAP 531 configuration tool.