ABB Network Partner AB
Pulse counter
Version 1.0-00
1MRK 580 187-XEN
Page 7 - 36
5Testing
The test of the Pulse Counter function requires at least a SPA (or LON)
connection to a station MMI including corresponding functionality. A
known number of pulses are with different frequency connected to the
pulse-counter input. The test should be performed for the settings opera-
tion = Off/On and for blocked/deblocked function. The Pulse Counter
value is then read by the station MMI.