Replacing AC Power Supplies
If you have ordered a server with power supply redundancy (two power supplies), you do not have to
power off the server to replace a power supply because they are redundant as 1+1.
Note
Do not mix power supply types or wattages in the server. Both power supplies must be identical.Note
Step 1
Remove the power supply that you are replacing or a blank panel from an empty bay:
a) Perform one of the following actions:
•
If your server has only one power supply, shut down and remove power from the server as described in Shutting
Down and Removing Power From the Server, on page 39.
•
If your server has two power supplies, you do not have to shut down the server.
b) Remove the power cord from the power supply that you are replacing.
c) Grasp the power supply handle while pinching the release lever toward the handle.
d) Pull the power supply out of the bay.
Step 2
Install a new power supply:
a) Grasp the power supply handle and insert the new power supply into the empty bay.
b) Push the power supply into the bay until the release lever locks.
c) Connect the power cord to the new power supply.
d) Only if you shut down the server, press the Power button to boot the server to main power mode.
Figure 38: Replacing AC Power Supplies
Power supply handle2Power supply release lever1
Cisco UCS C240 M5 Server Installation and Service Guide
89
Maintaining the Server
Replacing Power Supplies