2 Hardware Specifications and Wiring
DVP-PM Application Manual
2-1
2.1 Hardware Specifications
This chapter only provides information on electrical specification and wiring. For detailed information on program
design and instructions, please refer to Chapter 5 ~ 6. For how to purchase its peripheral devices, please refer to the
instruction sheet enclosed with the product.
2.1.1 Electrical Specifications
20PM 10PM
Power supply
voltage
100 ~ 240V AC(-15% ~ 10%), 50/60Hz ± 5%
Power supply fuse 2A/250VAC
Power consumption 60VA
DC24V current
output
500mA
Power supply
protection
DC24V; output short-circuit protection
Voltage withstand 1,500VAC (Primary-secondary); 1,500VAC (Primary-PE); 500VAC (Secondary-PE)
Insulation
resistance
> 5MΩ (all I/O point-to-ground: 500VDC)
Noise immunity
ESD: 8KV Air Discharge; EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication
I/O: 250V
Grounding
The diameter of grounding wire shall not be less that of L, N terminal of the power. (When
many PLCs are in use at the same time, please make sure every PLC is properly grounded.)
Environment
Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), pollution degree 2
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)
Vibration/shock
resistance
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27
(TEST Ea)
Weigh (approx. g.) 478/688
2.1.2 I/O Point Specifications
Input point specifications:
îš„ DVP20PM00D
Max. input
Terminal Description
Response
time
Current Voltage
START0, START1 For input signals of Start 10ms 6mA 24V
STOP0, STOP1 For input signals of Stop 10ms 6mA 24V
LSP0/LSN0,
LSP1/LSN1
Right limit input/left limit input 10ms 6mA 24V
A0+, A0-, A1+, A1-
MPG A-phase pulse input +, - (differential signal
input) (A1+, A1- are shared by Y and Z )
200kHz 15mA 5 ~ 24V
B0+, B0-, B1+, B1-
MPG B-phase pulse input +, - (differential signal
input) (B1+, B1- are shared by Y and Z)
200kHz 15mA 5 ~ 24V