W2940305 Rev 07 8/2019 Dover Fueling Solutions 37
5 Operation
5.1 Safety Items You Should Know
Know how to turn OFF power to the dispenser and submersible pumps in an emergency.
Use the pump for appropriate applications. Use only low viscosity fuels – diesel, including
biodiesel blends up to 20%; kerosene; gasoline, including standard oxygenated blends;
AvGas; and jet fuel (check with fuel supplier for any additional metal flow path restrictions
for AvGas and Jet fuel). Do not use the pump for pumping water or water-based liquids.
Note: Dispenser has not been evaluated for Biodiesel (above 20%), AvGas and Jet Fuel by
UL
.
Dispensers with the “E” Prefix utilize nickel-plating, hard anodizing, stainless steel,
special elastomers and a special fuel filter which have been used successfully for E85
compatibility. The modified components are UL Listed for gasoline, diesel, kerosene
(and similar products) and Ethanol blends up to and including E85.
Dispensers with the “D” Prefix are provided to handle Diesel Exhaust Fluid (DEF). These
units should only be used for dispensing DEF.
Make sure the dispenser is equipped with the proper accessories for the application and
product dispensed – for example, the proper filters and separators to ensure product
purity when refueling aircraft.
Inspect regularly, all external fuel carrying components such as, hoses, nozzles,
breakaways, etc., for damage or leaks.
Inspect regularly, the pump housing parts for damage or leaks.
Have all leaks or defects repaired immediately.
Test the emergency (shear) valve, by opening and closing several times, at least once
per year. Pressurize the line to be sure the valve holds the pressure.
Care should be taken to prevent fuel spillage. If spillage occurs, clean-up immediately.
Use of automatic safety nozzles prevents overfilling fuel tanks and avoids spilling fuel.
Avoid tipping the nozzle downward spilling excess fuel.
Sufficient lighting must be provided to allow safe use of the pump.
A clearly visible and identifiable Site Emergency Stop Switch must be provided at the site
to shut OFF power to all of the site’s dispensers and submersible pumps in case of an
emergency.
Stow hoses to prevent tripping.
Know the Hazardous Zone area around the dispenser.
Do not operate the dispenser in the presence of any source of ignition including lighted
cigarettes, electrical equipment, and running/hot engines.
Always keep an operating nozzle attended and do not re-enter the vehicle after beginning
the fueling sequence. Static buildup can be created from sliding in and out of the vehicle
seat. Static discharge by subsequently touching an operating nozzle can create a
hazardous situation.
Portable tanks (containers) of 12 gallons (45 liters) or less shall not be filled while they
are in or on a motor vehicle. See Warning information about this subject on the following
pages.
Wear safety goggles and protective clothes when dispensing any liquid that may be
potentially harmful or hazardous. Change saturated clothing and wash skin promptly with
soap and water.