GE Power Management
489 Generator Management Relay 6-45
6 COMMUNICATIONS 6.4 DNP COMMUNICATIONS
6
6.4 DNP COMMUNICATIONS 6.4.1 DEVICE PROFILE DOCUMENT
DNP 3.0
DEVICE PROFILE DOCUMENT
Vendor Name: General Electric Power Management Inc.
Device Name: 489 Generator Management Relay
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Device Function:
p
Master Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete
list is described in the attached table):
Binary Input (Object 1, Variations 1 and 2)
Binary Output (Object 10, Variation 2)
Binary Counter (Object 20, Variations 5 and 6)
Frozen Counter (Object 21, Variations 9 and 10)
Analog Input (Object 30, Variations 1, 2, 3, and 4)
Analog Input Change (Object 32, Variations 1, 2, 3, and 4)
Warm Restart (Function code 14)
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received: 292
Maximum Application Fragment Size (octets):
Transmitted: 2048
Received: 2048
Maximum Data Link Re-tries:
None
p
Fixed
p
Configurable
Maximum Application Layer Re-tries:
None
p
Configurable
Requires Data Link Layer Confirmation:
Never
p
Always
p
Sometimes
p
Configurable
Requires Application Layer Confirmation:
p
Never
p
Always
When reporting Event Data
p
When sending multi-fragment responses
p
Sometimes
p
Configurable
Timeouts while waiting for:
Data Link Confirm None
p
Fixed
p
Variable
p
Configurable
Complete Appl. Fragment None
p
Fixed
p
Variable
p
Configurable
Application Confirm None
p
Fixed
p
Variable
p
Configurable
Complete Appl. Response None
p
Fixed
p
Variable
p
Configurable
Others: (None)
Executes Control Operations:
WRITE Binary Outputs Never
p
Always
p
Sometimes
p
Configurable
SELECT/OPERATE Never
p
Always
p
Sometimes
p
Configurable
DIRECT OPERATE
p
Never Always
p
Sometimes
p
Configurable
DIRECT OPERATE - NO ACK
p
Never Always
p
Sometimes
p
Configurable
Count > 1 Never
p
Always
p
Sometimes
p
Configurable
Pulse On
p
Never Always
p
Sometimes
p
Configurable
Pulse Off Never
p
Always
p
Sometimes
p
Configurable
Latch On Never
p
Always
p
Sometimes
p
Configurable
Latch Off Never
p
Always
p
Sometimes
p
Configurable
(For an explanation of the above, refer to the discussion accompanying the point list for the Binary Output/Control
Relay Output Block objects)
Queue Never
p
Always
p
Sometimes
p
Configurable
Clear Queue Never
p
Always
p
Sometimes
p
Configurable
S
