4-32 489 Generator Management Relay
GE Power Management
4.7 S6 VOLTAGE ELEMENTS 4 SETPOINT PROGRAMMING
4
Volts/Hertz is calculated per unit as follows:
4.7.4 PHASE REVERSAL
The 489 can detect the phase rotation of the three phase voltages. A trip will occur within 200 ms if the Phase Reversal fea-
ture is turned on, the generator is offline, each of the phase-phase voltages is greater than 50% of the generator rated
phase-phase voltage and the phase rotation is not the same as the setpoint. Loss of VT fuses cannot be detected when the
generator is offline and could lead to maloperation of this element. If the VT type is selected as "None", the phase reversal
protection is disabled.
The formula for volts/hertz curve 2 is:
where:
T
= trip time in seconds
D
=
VOLTS/HERTZ TRIP DELAY
setpoint
V
= RMS measurement of Vab
F
= frequency of Vab
V
NOM
= generator voltage setpoint
F
S
= generator frequency setpoint
Pickup =
VOLTS/HERTZ TRIP PICKUP
setpoint
The V/Hz Curve 2 trip curves are shown on the right
for delay settings of 0.1, 0.3, 1, 3, and 10 seconds.
The formula for volts/hertz curve 3 is:
where:
T
= trip time in seconds
D
=
VOLTS/HERTZ TRIP DELAY
setpoint
V
= RMS measurement of Vab
F
= frequency of Vab
V
NOM
= generator voltage setpoint
F
S
= generator frequency setpoint
Pickup =
VOLTS/HERTZ TRIP PICKUP
setpoint
The V/Hz Curve 3 trip curves are shown on the right
for delay settings of 0.1, 0.3, 1, 3, and 10 seconds.
PHASE REVERSAL
[ENTER] for more
PHASE REVERSAL
TRIP: Off
Range: Off, Latched, Unlatched
ASSIGN TRIP
RELAYS (1-4): 1---
Range: Any combination of Relays 1 to 4
T
D
VF
V
nom
F
s
()Pickup×
-----------------------------------------------------
1
--------------------------------------------------------------= , when
V
F
----
Pickup>
0.1
1
10
100
1000
1.00 1.20 1.40 1.60 1.80 2.00
Multiples of Volts/Hertz Pickup
10
3
1
0.3
TIME DELAY SETTING
0.1
Time to Trip (seconds)
T
D
VF
V
nom
F
s
()Pickup×
-----------------------------------------------------


0.5
1
--------------------------------------------------------------------------= , when
V
F
----
Pickup>
0.1
1
10
100
1000
10000
1.00 1.20 1.40 1.60 1.80 2.00
Multiples of Voltz/Hertz Pickup
10
3
1
0.3
TIME DELAY SETTING
0.1
Time to Trip (seconds)
NOTE
Volts/Hertz
phase-phase voltage rated phase-phase voltage
frequency rated frequency
----------------------------------------------------------------------------------------------------------------------------------=
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE

Table of Contents

Other manuals for GE 489

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE 489 and is the answer not in the manual?

GE 489 Specifications

General IconGeneral
BrandGE
Model489
CategoryRelays
LanguageEnglish

Related product manuals